Pulse metering means reading a meter through electrical pulses. Each pulse is worth a fixed quantity: one litre, one Wh or one kWh.
A pulse value entered as 10 instead of 1 is enough to skew the entire consumption history by a constant factor. No alarm is raised, because the pulse transmitter works perfectly. Here is where the chain breaks and how to check it.
What is pulse metering and how does it work?
From meter to pulse: S0 output, volt-free contact and reed contact
A pulse meter relies on its pulse output, which your metering strategy should list. A turbine, a disc or an electronic measurement closes a contact at each fixed increment of volume or energy. Each change of state of the contact becomes a counted signal.
Did you know? On an electricity meter, this signal has its own standard: the requirements of the former IEC 62053-31, withdrawn in 2022, now sit in IEC 62052-11:2020[1][1]Standards and protocolsIEC, “IEC 62053-31:1998”, pulse output devices for two-wire connection, withdrawn on 11 April 2022 and taken over by IEC 62052-11:2020See in sources ↓. They only cover passive two-wire interfaces, the ones meter datasheets simply call a pulse output.
The type of interface changes how this signal is read. The S0 output, a two-wire opto-isolated transistor[2][2]Manufacturer documentationPolier, pulse output page, modular electricity meters and S0 outputSee in sources ↓, supplies no voltage: the input that reads it powers it. A volt-free contact is a potential-free switch. The reed contact, a glass capsule with flexible blades closed by a magnet, is fitted to the transmitters of water and gas meters.
What is a pulse value?
The pulse value, which datasheets also call the pulse weight, is the quantity one pulse represents. Manufacturers' datasheets show 1 L, 1 dm³[3][3]Manufacturer documentationIneo-Sense, pulse meter monitoring, fixed quantity per pulse depending on the meter typeSee in sources ↓, 1 Wh, 10 Wh or 1 kWh[2][2]Manufacturer documentationPolier, pulse output page, modular electricity meters and S0 outputSee in sources ↓.
The pulse value is read off the meter's rating plate; it is never assumed.
The notation also sets a trap: 1,000 imp/kWh means one pulse per Wh, not 1 kWh per pulse. From one flow meter to another, the same litre is not worth the same number of pulses. A wrong entry then multiplies the whole logged measurement by 10 or by 1,000.
Which pulse meters and which data links should you choose?
Water, gas, electricity, heat: the types of pulse meter
In a commercial building, four types of pulse meter share the panels:
- cold water meter and hot water meter, with a transmitter;
- gas in the boiler room, with a reed-contact transmitter;
- electrical sub-meter on DIN rail, S0 output;
- heating and cooling: thermal energy meter (heat meter).
The pulse says nothing about the device's accuracy class. For electricity, gas and water meters, that class falls under the Measuring Instruments Regulations 2016, the UK legal metrology framework that implemented the MID (Directive 2014/32/EU)[4][4]RegulationUK legislation, “The Measuring Instruments Regulations 2016” (SI 2016/1153)See in sources ↓. What remains is choosing how to bring the measurement back.
Pulses or a communication bus: which should you choose?
A pulse does not carry the register reading, only an increment. M-Bus, the meter bus defined by the EN 13757 series of standards (BS EN 13757 in the UK)[5][5]Standards and protocolsCEN, “EN 13757” series, communication systems for meters, including EN 13757-2+A1 (wired M-Bus) and EN 13757-4 (Wireless M-Bus)See in sources ↓, sends back an absolute register reading instead, just like Modbus.
| Criterion | S0 output or volt-free contact | Wired M-Bus | Modbus RTU | LoRaWAN radio or Wireless M-Bus |
|---|---|---|---|---|
| What is sent back | Increment of volume or energy | Register reading, flow, power, alarms depending on the device | Register reading, flow, power, alarms depending on the device | Register reading, alarms depending on the device |
| What is not sent back | Register reading, diagnostics, alarms | Depends on the model | Depends on the model | Depends on the model |
| Wiring and power | Two wires, loop powered by the input | Two wires, devices powered by the bus | RS-485 pair, one address per device | No wires, battery |
| Effect of an outage | Pulses lost | Register re-read on recovery | Register re-read on recovery | Register re-read on recovery |
| Register reading available to the BMS | No | Yes | Yes | Yes |
| When to keep pulses | Existing meters with no bus, device with no interface | Not applicable | Not applicable | Not applicable |
Keep pulses on an existing installation with no bus. On a new digital meter, a pulse output alone leaves the register reading on the display, out of the BMS's reach.
Advantages of a pulse meter and the real cost of a connection
The advantages of a pulse meter come down to wiring: two wires and no address to configure[6][6]Manufacturer documentationVoltebox, pulse output page, two-wire connection with no addressSee in sources ↓. Accurate measurement is still down to the device, not to its output.
Beyond the price of a pulse meter, the quote sets two options against each other: rewire and configure, or replace with a communicating meter. Replacing a healthy device for the sole purpose of gaining a bus is not always justified. The real cost of a botched connection remains the wrong history, which the reporting tool displays without a flicker.
How do you connect a pulse output to a BMS?
Controller input, pulse concentrator or IoT sensor: where the pulses end up
To connect a pulse meter, there are three destinations. The first is a digital input on a controller, a small industrial computer with no screen: it counts the pulses without knowing the register reading. The pulse module, also called a concentrator, goes further: it converts its inputs to a bus and keeps a local register reading.
The LoRaWAN IoT sensor, a long-range, low-data-rate radio, fits directly onto the transmitter. It also keeps a register reading and transmits it remotely, which opens the way to automatic meter reading without pulling a cable.
Installing and wiring a pulse transmitter at the panel
Before installing a pulse meter, ask the integrator how they wire the pulse transmitter:
- external power supply for the S0 loop;
- polarity of the output;
- PNP or NPN input type;
- pull-up resistor;
- cable length and screening;
- minimum pulse duration accepted;
- mounting of the module on DIN rail.
When the input does not supply the voltage itself, an external power supply closes the loop. The following diagram shows this arrangement, terminal by terminal.
- The + of the external power supply goes to terminal S0+.
- Terminal S0- goes to the controller's digital input.
- The controller's common returns to the - of the power supply.
This diagram works as a checklist: each wire has its polarity, each input its rest state.
Configuring a pulse meter in the BMS and reading the register
To configure a pulse meter, two steps come before any reading. First, enter the pulse value and its unit in the BMS front end. Then align the starting register value with the meter's mechanical register, otherwise the gap stays frozen in the entire history.
That leaves reading a pulse meter. On site, the mechanical dial or the display gives the meter's figures. A totaliser adds up the pulses received[7][7]Manufacturer documentationCompteur-energie.com, pulse meters, displays, registers and totalisers, pulse totaliserSee in sources ↓. The BMS register reading, for its part, is only right if the first two steps were done right.
Not sure which of your meters send back a correct register reading? We check them one by one, from the pulse value entered to the logged reading.
Outages, wrong pulse values, drifting registers: the limits of pulse metering
What happens during an outage or when pulses are lost?
A controller that is switched off does not see the pulses emitted while it is down: the quantity consumed disappears from the history. An input with too long a response time misses pulses when the frequency rises. Reed contacts bounce, so a single change of state is sometimes counted twice.
Pulse output or volt-free contact, the pulse carries no register reading: nothing catches up on its own.
How do you check pulse metering?
A clean history on screen can hide silent faults. The following checklist lists five that a curve does not show, each with its symptom and the test to ask your FM contractor for. Tick the ones they have already ruled out, with evidence.
Five faults a curve does not show
The most telling test remains the joint reading: the register read on the display or the totaliser, compared on the same day with the BMS value. On water consumption, a gap of a factor of 10 almost always points to the pulse value entered at the input. The meter's own measurement is rarely at fault.
Making metering data reliable with Foobot
Meter data reliability: gaps, duplicates and drift in the history
A metering history builds up faults that nobody looks at: disconnections, data gaps, duplicates, invisible drift. Meter data reliability, a deliverable of our BMS advisory, tracks them down point by point. We qualify every meter on the site before any analysis. Energy management or a service charge allocation built on unqualified data inherits their errors.
Handover and warranty year: testing every metering input
A BMS handed over with no defects listed has not necessarily been tested. During Handover / Warranty Year (the defects liability period), we simulate pulses on each metering input, with the pulse output disconnected, then check the change of state in the BMS front end. Defects are only closed after this test. A quote for remedial work can then be discussed on the evidence.
Reliable register readings before any control: IPMVP measurement and AI Control
An energy saving can only be measured under the IPMVP protocol on accurate meters. At Valeo, the −28.6% reduction in HVAC consumption was established this way, on verified data. AI Control comes next, only if the building has real energy complexity. Accurate measurement first, optimisation after.
Before signing off a report, trace the path of the pulses
A consumption report is never more accurate than the first link in its chain. Between the meter's rating plate and the cost allocation sheet, each pulse goes through five stages. Two steps decide everything: entering the right pulse value and aligning the starting register value.
Before approving the next energy report, ask your FM contractor for a joint reading, meter by meter. Pulse metering in your BMS will then become a sound basis for connecting an EMS to the BMS, starting with the free Foobot EMS. We can carry out this first reading with you.
FAQ - pulse metering
How do you wire a meter with a pulse transmitter?
A meter with a transmitter connects with two wires to a digital input on a controller or to a pulse module. Depending on the transmitter, an external loop power supply is needed. When installing a pulse meter, check the polarity too.
What is the difference between a communicating meter and a pulse meter?
A pulse meter emits an increment, with no register reading. A communicating digital meter, a device connected to a Modbus, M-Bus or radio network, transmits its absolute register reading and its alarms. After an outage, only the communicating meter can be re-read without loss.
Can an old pulse meter be connected?
Yes, if its transmitter still works. To connect an old pulse meter, note the pulse value from the rating plate. Then align the BMS register with its mechanical dial. Without these two steps, the history is wrong from day one.
How do you read a pulse meter remotely?
Remotely, there are two routes. A LoRaWAN IoT sensor fitted on the transmitter sends a reconstructed register reading. A BMS input logs the pulses received. Reading a pulse meter on its display remains the reference for checking both.
What is an S0 pulse output?
The S0 pulse output is a two-wire opto-isolated transistor, found on modular electricity meters mounted on DIN rail[2][2]Manufacturer documentationPolier, pulse output page, modular electricity meters and S0 outputSee in sources ↓. This pulse output supplies no voltage: the input that reads it powers the loop.
What does one pulse correspond to?
A pulse represents a fixed quantity: 1 litre of water, 1 Wh or 1 dm³ of gas depending on the meter[3][3]Manufacturer documentationIneo-Sense, pulse meter monitoring, fixed quantity per pulse depending on the meter typeSee in sources ↓. This pulse value determines how water or energy consumption is calculated. Note: 1,000 imp/kWh means one pulse per Wh.
Sources and references
7 sources.- [2]Polier, pulse output page, modular electricity meters and S0 output↑ 1 2 3
- [3]Ineo-Sense, pulse meter monitoring, fixed quantity per pulse depending on the meter type↑ 1 2
- [6]Voltebox, pulse output page, two-wire connection with no address↑
- [7]Compteur-energie.com, pulse meters, displays, registers and totalisers, pulse totaliser↑